Summary: The National Fire Protection Association (NFPA) sets standards for fire safety systems. Essential publications outlining sprinkler system installation and fire pump testing criteria are NFPA 13 and NFPA 24. Navigating these rules might be difficult; this blog seeks to streamline matters for you! We have prepared responses to some of the most frequently asked issues about sprinkler spacing close to barriers, fire pump testing protocols, and particular storage type unique considerations. This blog will provide you with insightful analysis from the most recent versions of NFPA 13 (2022) and NFPA 24 (2022), regardless of your position—contractor, building inspector, or just someone interested in fire safety.

1. 3 Times Rule- Standard Spray Sprinkler. Description- Section 8.6.5.2.1.3 (B) in the 2013 version of NFPA 13 states a maximum distance of 24 inches between a sprinkler and a vertical impediment like a column. Starting in 2016, further versions eliminated this maximum limit, so depending on the dimensions of the obstacle, one must follow the ``three times rule``. For a 10-inch column, for instance, the sprinkler would have to be placed 30 inches away to comply. Question 1. Regarding Figure 8.6.5.2.1.3 (B) of NFPA 13 (2013), what is the minimal distance of a sprinkler to a column independent of the column's dimension? Is that 24 inches?

Answer: Indeed, following Section 8.6.5.2.1.3 (three-times rule) of the 2013 NFPA 13, the maximum distance between a sprinkler and an impediment in the vertical orientation (column) is 24 inches. Section 8.6.5.2.1.3 (B) contains this need; the maximum clear space needed is 24 inches.

It should be mentioned that the 2016 edition (and all following editions) of NFPA 13 modified this criteria. Beginning with the 2016 edition, the 24-inch limit clear distance was eliminated for vertically oriented impediments, including columns. This means that for obstacles like columns, the three times rule determines the minimum space between the sprinkler and the column. If a column measured 10 inches by 10 inches, for instance, the sprinkler would have to be positioned 30 inches from the column to satisfy 8.6.5.2.1.3.

This article from the October 2, 2015 issue #328 of NFSA’s TechNotes helps to clarify this change: Changes in the 2016 Edition of NFPA 13 Installation Criteria. Minimum distance from an obstruction in vertical orientation (8.6.5.2.1.3). Applying the guidelines of 8.6.5.2.1.3, sometimes referred to as the “three times rule,” the maximum clear space of 24 inches has been reduced for vertical orientation obstructions, including columns. Work by the NFSA E&S committee work group on shadow regions and fire testing has revealed that the “three times rule” allows a maximum clear distance of 24 inches, which is not ideal. This experiment revealed that the fire may not be under control when sprinklers are located near significant obstacles using this maximum clear distance allowance.

Since this experiment just focused on vertical columns, the removal of the maximum clear distance is confined to vertical orientational obstacles.

For other sprinkler kinds as well, this rule—which is “three times rule”—and “four times rule” were changed similarly.

This adjustment simply removes the maximum clear distance to obstructions in the vertical orientation, such as columns, and does not alter the base three times rule or four times rule. Only when applying this rule to significant vertical impediments in excess of 8 inches (or 9 inches for the four-times rule) would this suggested alteration become relevant. These big columns can still be treated using the three- or four-times method without considering a maximum clear-distance allowance of 24 or 36 inches.

2. Sprinkler Omissions in Closets. Description- Under five square feet, a closet exists in a light-hazard space—a corridor. Question 2. Given the limited space in this closet in a structure protected by the 2016 edition of NFPA 13, is it reasonable to leave out a sprinkler?

Answer:Although sprinkler installation is usually necessary in closets, occupancy or use of the structure will determine some exclusions.

NFPA 13 excludes closets less than 24 square feet in hotel and motel living quarters as well as in hospital patient rooms less than 6 square feet. Outside of these particular examples, sprinklers are usually needed in closets of any size. Under 400 cubic feet, there is an installation exception for closets, allowing a sprinkler to be positioned in the ceiling without regard for impediments.

There are further exclusions for confined areas; these only relate to sprinklers in concealed areas.

3. Fire Pump Testing. Description- Section 14.2.6.2.4 permits testing a fire pump at 130% of its rated flow in line with NFPA 20 (2016 edition) if it can still meet the maximum flow demand required by the fire protection system. This is acceptable if the current water supply avoids reaching 150% of the specified flow, therefore guaranteeing that the pump's performance satisfies system design and operational criteria during acceptance testing. Question 3. One of the projects shows that, when we go to test, the fire pump will only be able to flow around 130% of its rated flow. We would like to verify that this is permissible per Section 14.2.6.2.4?

Answer: Indeed, this is allowed by NFPA 20, 2016 edition, Section 14.2.6.2.4, provided the maximum flow demand of the fire prevention system(s) can be satisfied as well.

Section 14.2.6.2 indicates that where the maximum flow available from the water supply cannot provide a flow of 150 percent of the rated flow of the fire pump, it shall be operated at the greater of 100 percent of the rated flow or the maximum flow demand of the fire protection system(s) maximum allowable discharge to determine their acceptance.

Section 14.2.6.2.4 considers this an acceptable test even if 150% of the rated flow of the pump cannot be reached due to the available water supply, if acceptance testing the fire pump at 130% of the rated flow also satisfies the maximum flow demand of the fire protection system(s).

Section 14.2.6.2.4.1 therefore indicates that, provided the pump discharge exceeds the fire protection system design and flow rate, this reduced capacity will represent an acceptable test.

4. Protection Criteria: Class I Through Class IV Commodities Stored Up to 12 feet in Height. Description- In NFPA 13 (2019 edition), Section 4.3.1.7.1 says that Table 4.3.1.7.1 can be used to find out how much sprinkler discharge is needed for low-piled storage up to 12 feet high, which includes non-miscellaneous storage classes I to IV. This table supports the density/area approach described in Section 19.3.3.2 for ceiling-only sprinkler protection, alongside Figure 19.3.3.1. Question 4. Does NFPA 13, 2019 have anything allowing us to use Table 4.3.1.7.1, which is titled Discharge Criteria for Miscellaneous Storage? Up to 12 feet in Height for non-miscellaneous storage (Class I – IV) that does not exceed 12 feet in height?

Answer: In fact, Section 4.3.1.7 of NFPA 13, 2019 edition, shows the protection standards for low-piled and assorted storage in 4.3.1.7.1.

Storage covered by ceiling sprinklers only should be chosen from Table 4.3.1.7.1 and Figure 19.3.3.1.1 in line with the density/area approach of 19.3.3.2. Table 4.3.1.7.1 Discharge Criteria for Miscellaneous Storage has a header noting “Table 4.3.1.7.1 Discharge Criteria for Miscellaneous Storage.”

Up to 12 feet (3.7 m) in height, as stated in the body of the standard in Section 4.3.1.7, this table also applies to low-piled storage.

5. Open-Grid Ceiling Sprinklers Above and Below Ceiling. Description- One cannot consider a waffle grid ceiling as an open-grid ceiling since it is deeper than the least dimension of the aperture. Above the ceiling and beneath the waffles were installed. Question 5. Should the water shield of the lower-level sprinkler help to prevent cold soldering?

Answer: Indeed, it is allowed and advised to install intermediate type sprinklers with water shields for sprinklers installed below open grid ceilings when sprinklers are also installed above those open grid ceilings. Although not specifically relevant, NFPA 13 (2016) Section 8.5.5.3.4 states that sprinklers placed below open grating must be either otherwise insulated from discharge from above or intermediate/rack type sprinklers. Although this part speaks to open grating walkways, the intention still holds for open grid ceilings.

6. Tire Storage Piling Method. Description- Table 18.4(a), (1)(a) in the 2013 edition of NFPA 13 details a piling technique of pyramid piles on-side. Question 6. Is this suggesting that the tires ``have`` to be piled on the side, or is another possible? The only way tires could be pyramid piled is on-side.

Answer: Table 18.4(a), (1)(a) identifies the storage arrangement as “Pyramid piles, on-side,” thereby referring to tires kept in a pyramid arrangement which offers stability (see definition in 3.9.4.8) and the tires placed on their sides. The tires must be kept on-side if one wants to use the design criterion for “Pyramid piles, on-side”.

One cannot substitute on-side for pyramid piles. Should this be the case, it would be stated as “Pyramid piles or on-side.” For instance, see Table 18.4(a), (3). This part is detailing palletized movable rack storage with tires kept either on-side or on-thread. As can be seen, “on-side or on-thread” descriptions abound for these different storage configurations.

Pyramid piles could incorporate tires kept either on-side or on-threat to address the second question. As it happens,. Exhibit 3.45 of the 2013 Automatic Sprinkler Systems Handbook

shows a pyramid stack of tires kept on thread.

7. Regenerative Air Dryer. Description- This topic asks whether a C-factor of 120 in a chilled environment with galvanized pipes can be maintained using a regenerative air dryer instead of nitrogen. Question 7. Is it allowed to use a regenerative air dryer to supply air in a refrigerated environment as a gaseous medium with galvanized pipes instead of nitrogen to keep a c-factor of 120?

Answer: No. The 2022 edition of NFPA 13 permits, in Section 8.8.2.4 (2), a regenerative air dryer as an alternative to nitrogen. But Table 28.2.4.8.1 just gives a C value of 120 using nitrogen. Consequently, the response to your query is no; a C-factor of 120 is not allowed using merely a regenerative air dryer.

Nitrogen must be utilized in line with Section/Table 28.2.4.8.1 if one wants to apply the C factor of 120. Some changes were made to Section 28.2.4.8.1 in the 2022 edition. Condition #13 says that the C value of 120 is only allowed when nitrogen is added to the system according to Section 8.2.6.9 and all the other conditions in this section are met. It should be noted that, should a vapor corrosion system be adopted, the 2025 edition of NFPA 13 will probably allow a C-factor of 120. The 2025 edition will not especially target the regenerative air dryer, though.

8. Design Criteria for Exposed Expanded Plastic. Description- This question asks whether a C-factor of 120 in a chilled environment with galvanized pipes can be maintained using a regenerative air dryer instead of nitrogen. Question 8. In the 2019 edition of NFPA 13, what design standards apply to the storage of exposed expanded plastic up to 35 feet and a maximum ceiling height of 40 feet?

Answer:  The expanded Group A plastics criteria for employing K-25.2 ESFR sprinklers in Section 23.7 have been highlighted in the 2019 edition of NFPA 13. It calls for a 12-sprinkler design ( Section 23.7.5) with 60 psi (23.7.6) for each sprinkler. For this use—every 16 1⁄2 feet—a solid vertical barrier is needed. 23.7.8 For further information, kindly review this part from beginning to end.

9. Exterior Canopy. Description- A project calls for an outside canopy spanning more than four feet with non-combustible coatings but exposed plywood backing. Not one additional ingredient is flammable. Question 9. On the plywood, may a field applied coating following NFPA 703 be utilized to avoid placing sprinklers inside and below the canopy?

Answer:  Field-applied coatings do not satisfy the requirements in Section 8.15.1.2.11 or 8.15.7 for fire retardant treated wood (FRTW). These guidelines apply especially to FRTW and do not cover fire retardant coatings applied in the field. Defined in the 2009 NFPA 703, Section 3.3.2, NFPA 13 allows the use of NFPA 703-compliant FRTW, which is defined as a “wood product imbued with chemicals by a pressure process.” Consequently, FRTW cannot be attained by field application and must, by definition, be pressure treated in a production environment.

Although NFPA 703 offers standards and specifications for field-applied coatings, these coatings do not fit as FRTW since they do not satisfy the pressure impregnation need. Consequently, untreated plywood in the hidden area is regarded as combustible, and field-applied coatings are insufficient to prevent the sprinkler installation. Still, covering the plywood with a limited-combustible material—like drywall—would be a reasonable substitute for skipping sprinklers in this area. Without depending on field-applied coatings, this method guarantees adherence to NFPA 13 and other requirements.

10. NFPA 24 - Control Valves. Description- Section 6.2.1 of NFPA 24 (2022 edition) questions if every line branching off a site fire loop requires a control valve. Question 10. A site fire loop feeding several fire risers. Does every line off of the site loop require a control valve per 6.2.1 of the NFPA 24 2022 edition?

Answer: Truly, every “lead-in” to a fire protection system fed by a site fire loop requires a control valve.

Section 6.2.1 notes that “each pipeline from each water supply” has to be furnished with a control valve. Although the word “pipeline” is not defined in NFPA 24, it is described in other NFPA publications as: “A length of pipe including pumps, valves, flanges, control devices, strainers, and/or similar equipment for conveying fluids,” thereby including the lead-ins to a fire protection system.

Section 6.2.9 of the 2025 edition of NFPA 24 also stipulates that “all connections to private fire service mains for fire protection systems” must have a control valve and offers 8 alternatives to support the above.

11. Fire Pump Acceptance Testing. Description- This topic questions whether pitot gauges for fire pump acceptance testing could be replaced with a closed-loop flow meter instead of discharging water. Question 11. Can a closed looping flow meter be used instead of running water and testing with pitot gauges for fire pump acceptance testing?

Answer: Yes, NFPA 20 mandates the first acceptance test to incorporate known nozzles and a measurable discharge pressure together with flow to the atmosphere. The initial fire pump acceptance test cannot measure the flow using a closed loop system with discharge back to the suction side of the fire pump or a flow meter. This guarantees the flow rate’s accuracy and covers testing of the water supply to the pump.

12. Obstructions Along a Wall. Description- A project consists of under 24-inch soffits that run along a wall. Under Section 12.1.10.2 (b), we omitted including a residential sprinkler under the soffit. With our household sprinklers spaced 16 by 16, 1⁄2 of S would be 8 feet. Question 12. The sprinkler's highest range from the wall is eight feet. The sprinkler is allowed to be how close to the soffit?

Answer: Applying the NFPA 13 (2022) Section 12.1.10.2 criteria allows you to install sprinklers without respect to the soffit blockage; the sprinklers must, however, be spaced adequately to the wall behind the soffit. Although you are allowed to be closer to the soffit, you have to still be a minimum of 4 inches apart for maintenance needs. “Sprinklers shall be located a minimum of 4 in. from an end wall,” Section 12.1.8.6.1 notes. Although this is a soffit rather than a wall, the required 4 inches serve to make future removal or reinstallation of the sprinkler possible. This would still be vital, considering the distance to the soffit.

Courtesy: Roland Asp, CET, TechNotes